SmartServer 2.2 FT

The SmartServer is a versatile controller, router, and smart energy manager that connects control devices to IP-based applications such as building automation, enterprise energy management, demand response programs, and high-value remote asset management programs.

Key Features

  • Provides unprecedented connectivity with built-in drivers for industry-standard protocols including LON free topology (FT-10), IP-852, Modbus RTU, Modbus IP, M-Bus, digital I/O, pulse count, and SOAP/XML Web services interfaces, as well as available support for BACnet IP. The BACnet IP driver is available from www.connect-ex.com. LON power line (PL) versions are also available (http://www.echelon.com/products/smartserver_pl). Additional interfaces can be developed with custom driver support.
  • Manages up to 300 devices as a standalone network manager—or joins IzoT Net Server, OpenLNS, and LNS-managed networks with seamless server integration.
  • Supports automatic device discovery, configuration, and commissioning.
  • Provides an open platform for both local monitoring and control as well as integration with enterprise applications for energy management of commercial buildings, branch offices, street lights, solar arrays, and others.
  • Supports customization with support for custom apps such as energy optimization, data analysis, and room and lighting control apps.
  • Includes built-in Web-user and Web-services interfaces for scheduling, alarming, data logging, meter reading, and custom applications.
  • Supports development of custom Web pages with the included i.LON® Vision tool.

Tech Specs

PC Requirements

 

Minimum Requirements for Echelon Enterprise Services

15GHz 32-bit (x86) or 64-bit (x62) processor, 1GB RAM, DVD-ROM drive, 250MB of free disk space


Operating System

64-bit and 32-bit versions of Windows 10, Windows 81, Windows 8, and Windows 7, and 32-bit versions of Windows XP


SmartServer FT Hardware

 

Processor

MIPS32™, 264MHz

Memory

  • 64MB flash memory
  • 64MB RAM

Channel Type

TP/FT-10 free topology twisted pair

LonWorks Network Connector

Screw terminals



Operating Input Voltage

100 – 240VAC (-6%/+10%), 50/60Hz

Power Consumption

<15 watts

Controls

Service button, Reset button

Indicators

  • Power On/Wink
  • Ethernet link
  • Ethernet activity, 10/100 Mbps
  • LON Service, Tx, Rx
  • 2 digital inputs
  • 2 relay outputs
  • 2 metering inputs
  • Remote Network Interface (RNI) connection status

Ethernet Port

10/100BaseT, auto-selecting, auto polarity

Ethernet Connector

RJ-45, 8 conductor

Serial Ports

  • 1 isolated RS-485 port
  • 1 EIA-232 port

Serial Connectors

Screw terminals

Modem

Optional V90 internal analog modem (Model 72012R-440)

Modem Connector

RJ-11, 6 conductor

Supported External Modems

  • Cinterion MC75
  • Cinterion MC63i
  • ETM9300 1 3G
  • Janus Terminus GSM864Q
  • Multitech MTCBA-G-F1
  • Siemens 35 to 45 Series
  • Siemens MC55 3G
  • Siemens MC75 EDGE

Console Port

EIA-232

Console Connector

DB-9

Digital Inputs

2 optically isolated dry contact inputs, 30V AC/DC

Digital Input Connector

Screw terminals

Relay Outputs

2 SPST relays rated at 240VAC @ 10A or 24VDC @ 10A

Relay Output Connector

Screw terminals

Impulse Meter Inputs

DIN 43 864 (open terminal voltage ≤12VDC max; max current ≤ 27mA)

Impulse Meter Input Connector

Screw terminals



Operating Temperature

0 to +50°C


Non-operating Temperature

-40 to +85°C


Operating Humidity (non-condensing)

10 to 90% RH @ 50°C



Non-operating Humidity (non-condensing)

5 to 90% RH max @ 50°C



Dimensions

351 in (H) x 547 in (W) x 260 in (D); 8TE DIN, 89 cm (H) x 138 cm (W) x 66 cm (D)

EMC

FCC Part 15 Class B, EN55022 Class B, EN55024, CISPR 22 Class B, VCCI Class B

Agency Listings

UL 60950, cUL C222 No 60950-00, TÜV EN60950, CE, C-Tick

Mounting

DIN, Enclosure 8TE

Connect with us.